			<item>
		<title>APC UPS Time Remaining Value for N-Able</title>
		<link>http://www.michaelcolson.com/2007/02/09/apc-ups-time-remaining-value-for-n-able/</link>
		<comments>http://www.michaelcolson.com/2007/02/09/apc-ups-time-remaining-value-for-n-able/#comments</comments>
		<pubDate>Fri, 09 Feb 2007 15:43:41 +0000</pubDate>
		<dc:creator>michael</dc:creator>
				<category><![CDATA[apc]]></category>
		<category><![CDATA[n-able]]></category>

		<guid isPermaLink="false">http://mcolson.wordpress.com/?p=45</guid>
		<description><![CDATA[The APC service time remaining is calculated in 1000 of time ticks. the calculation is as follows.
The Time remaining threshold is currently showing a Value of 342.00 Time Ticks.

The mathematical calculation to determine how many minutes there are left will be
342 x 1000 = 342000
342000 / 100 time ticks =  3420 seconds
3420 seconds / 60 [...]]]></description>
			<content:encoded><![CDATA[<p>The APC service time remaining is calculated in 1000 of time ticks. the calculation is as follows.</p>
<p>The Time remaining threshold is currently showing a Value of 342.00 Time Ticks.</p>
<p><span id="more-26"></span></p>
<p>The mathematical calculation to determine how many minutes there are left will be</p>
<p>342 x 1000 = 342000<br />
342000 / 100 time ticks =  3420 seconds<br />
3420 seconds / 60 = 57 minutes</p>
<p>time remaining in minutes is 57 min.</p>
<p>The following illustrates the custom thresholds for:</p>
<table border="0" cellspacing="0" cellpadding="0" width="100%">
<tbody>
<tr>
<td>Normal</td>
<td>10 min or more</td>
</tr>
<tr>
<td>Warning</td>
<td>5 min &#8211; 10 min</td>
</tr>
<tr>
<td>Failed</td>
<td>5 min or less</td>
</tr>
</tbody>
</table>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelcolson.com/2007/02/09/apc-ups-time-remaining-value-for-n-able/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>SmartSlot devices with an APC Smart-UPS</title>
		<link>http://www.michaelcolson.com/2007/01/19/smartslot-devices-with-an-apc-smart-ups/</link>
		<comments>http://www.michaelcolson.com/2007/01/19/smartslot-devices-with-an-apc-smart-ups/#comments</comments>
		<pubDate>Fri, 19 Jan 2007 15:18:53 +0000</pubDate>
		<dc:creator>michael</dc:creator>
				<category><![CDATA[apc]]></category>

		<guid isPermaLink="false">http://mcolson.wordpress.com/?p=43</guid>
		<description><![CDATA[Question
How do I insert a SmartSlot device in a Smart UPS or Matrix UPS?

Answer
Warning: If SmartSlot accessories are installed into the UPS without following these instructions, a risk exists that the UPS could suffer damage.
It is very important that the Smart UPS be completely off before inserting or removing any SmartSlot card.
Please carefully follow the [...]]]></description>
			<content:encoded><![CDATA[<p><strong>Question</strong><br />
How do I insert a SmartSlot device in a Smart UPS or Matrix UPS?</p>
<p><span id="more-24"></span></p>
<p><strong>Answer</strong><br />
Warning: If SmartSlot accessories are installed into the UPS without following these instructions, a risk exists that the UPS could suffer damage.</p>
<p>It is very important that the Smart UPS be completely off before inserting or removing any SmartSlot card.</p>
<p>Please carefully follow the directions below in order to prevent undesirable behavior of or damage to the UPS:</p>
<ol>
<li>Ensure all loads powered by the UPS are properly shut down and turned off.</li>
<li>Shut down the UPS via the front panel by pressing the button labeled &#8220;0&#8243;.</li>
<li>Disconnect the UPS&#8217; input power cord from the wall receptacle.</li>
<li>Press and hold the &#8220;0&#8243; button for about 4 seconds and listen for a click from inside the unit. At this point the green sensitivity LED on the back of the unit will turn off, indicating that the unit is completely powered off. However, if the unit were previously set to low sensitivity, it is harder to notice the change in brightness.</li>
<li>Now it is safe to insert or remove the SmartSlot accessory card into/from the UPS SmartSlot.</li>
</ol>
<p>*** For a Matrix UPS, you need to put the Matrix into bypass by the screw on the back.<br />
Undo the screw all the way until the front display turns off. Once the display is off, the Matrix is in bypass.</p>
<p>From:  <a href="http://nam-en.apc.com/cgi-bin/nam_en.cfg/php/enduser/std_adp.php?p_faqid=946">http://nam-en.apc.com/cgi-bin/nam_en.cfg/php/enduser/std_adp.php?p_faqid=946</a></p>
]]></content:encoded>
			<wfw:commentRss>http://www.michaelcolson.com/2007/01/19/smartslot-devices-with-an-apc-smart-ups/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>